8 Operation
Maschinenfabrik Reinhausen GmbH 2020
132
3587317/21 EN
TAPCON
®
If you enter event number 500, the link is disabled.
8.10 Control of the motor-drive unit
The following parameters let you configure control of the motor-drive unit.
You can set the following:
▪ Switching pulse
▪ Motor runtime
▪ Switching direction
Settings
Parameters
Motor co...nit
Name
Value
Switching pulse type
Time-controlled pulse
Switching pulse time
1.5 s
Switching pulse pause
2.5 s
Activate motor runtime monitoring
Off
Motor runtime
6 s
Activate switching direction moni...
Off
Switching direction
Standard
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
03.02.2020 08:09
Figure 100: Motor control unit
► Go to
Settings > Parameters > Motor and control cabinet > Torque
monitoring
.
8.10.1 Setting the switching pulse for controlling the motor-drive unit
You can use the parameters Switching pulse type, Switching pulse time and
Switching pulse pause to adapt the device switching pulse to the require-
ments of the motor-drive unit controller.
1. Go to
Settings > Parameters > Motor and control cabinet > Motor
control
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Switching pulse type
You can use this parameter to toggle the switching pulse between a continu-
ous pulse or a time-controlled switching pulse.