![MR TAPCON Скачать руководство пользователя страница 81](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346081.webp)
7 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
81
3587317/21 EN
TAPCON
®
7.5.1 Checking measured values and status of digital inputs and
outputs
Upon commissioning the device, check whether the measured values and
status of digital inputs and outputs are plausible. To do so, use an additional
measuring device if necessary in order to check the individual measured val-
ues.
To display the status of the digital inputs and outputs, proceed as follows:
1. Go to
Information > Hardware
.
2. Select the individual
assemblies
one after another and check the individ-
ual measured values or the status of digital inputs and outputs.
3. If errors arise, check the measurement path and the wiring [
7.5.2 Testing a control function
This section describes how you can check the device's control functions:
ü
Supply voltage must be present.
1. Press
to select manual mode.
2. Set transmission ratio for voltage transformer, current transformer, and
transformer circuit.
3. Measure actual voltage and compare with the measured value displayed
on the device's main screen.
4. Select the
Measured values
menu item to display the operating values
for current and power and compare them with the values of the operation
measurement instruments.
5. Control the on-load tap-changer manually using the
or
keys
until the measured voltage U
actual
reaches the desired voltage U
desired
("de-
sired value 1").
6. Set desired value to the value you want [
7. Set bandwidth depending on step voltage [
8. Set delay time T1 to 20 seconds [
9. Set time response T1 to linear [
10. Press
to raise the on-load tap-changer 1 step.
11. Press
to select auto mode.
ð
If the actual voltage is outside the bandwidth, the device returns the
on-load tap-changer to the original operating position after 20 sec-
onds.
12. Press
to select manual mode.
13. Press
to lower the on-load tap-changer 1 step.
Содержание TAPCON