8 Operation
Maschinenfabrik Reinhausen GmbH 2020
215
3587317/21 EN
TAPCON
®
Behavior
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting
Behavior
Off
The limit value is not monitored.
Auto blocking
Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Table 77: Behavior when an event message is issued
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
8.19.9 Switching interval monitoring
You can use this function to monitor the typical tap-change behavior of your
transformer. Furthermore, you can set the number of consecutive tap-
change operations permissible in auto mode within a defined time period.
You can have the following operations monitored:
▪ Total operations: Total RAISE operations and LOWER operations
▪ LOWER operations: Total LOWER operations
▪ RAISE operations: Total RAISE operations
Settings
Parameters
Total sw...ing
Total
Lower
Raise
Total No. ops
Time interval
Event duration
Response
Count behavior
-
25
1440.0 min
1.0 min
Auto blockin...
10
5.0 min
15.0 min
Off
Auto block. ...
10
5.0 min
15.0 min
On
Auto block. ...
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
29.01.2020 15:45
Figure 148: Switching interval monitoring
1. Go to
Settings > Parameters > Grid > Switching interval monitoring
.
2. Select the desired parameter.