8.18.2 Configuring parallel operation
In the
Parallel operation
menu item, you can set the parameters needed for
parallel transformer operation.
Settings
Parameters
Parallel...ion
Name
Value
Activating parallel operation
On
Parallel operation method
Master
CAN bus address
1
Circulating reactive current sens...
0.0 %
Circulating reactive current bloc...
20.0 %
Desired power factor
0.9
Desired load stress type
Inductive
Master/follower current blocking
Off
Maximum tap difference
1
Master/follower switching charact...
Sequential
Error if no communication present
No error
Behavior if no communication pres...
Independent regulation
Parallel operation error delay ti...
10 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
03.02.2020 08:09
Figure 129: Parallel operation
1. Go to
Settings > Parameters > Grid > Parallel operation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Activating parallel operation
You can use this parameter to activate parallel operation.
Parallel operation method
You can use this parameter to set the parallel operation method. You can
select the following options:
Option
Description
Master
The device is designated as
the master.
tion 8.18.1.1, Page 180] par-
allel operation method
Follower
The device is designated as
the follower.
Auto. tap synchroniza-
tion
Automatic assignment of
master or follower.
If a master is not detected,
the device with the lowest
CAN bus address is auto-
matically designated as the
master. All other devices are
designated as followers.