8 Operation
Maschinenfabrik Reinhausen GmbH 2020
193
3587317/21 EN
TAPCON
®
Pos</Pos> follower (optional)
You can use these parameters to set the highest and lowest permissible tap
position of the follower. With the tap stagger parallel operation method, the
device uses the following parameters for tap position monitoring [
8.19.5, Page 209] of the master and follower:
Parameter
Pos< (follower)
Pos> (follower)
Behavior limit value
Auto blocking for lower tap Auto blocking for raise tap
Delay time
0 s
Table 67: Tap position monitoring
8.18.3 TAPCON® 2xx retrofit
The TAPCON® 2xx retrofit function allows you to operate the device in par-
allel operation with existing devices. Parallel operation with the following ex-
isting devices is supported:
▪ TAPCON® 230 pro/expert
▪ TAPCON® 240
▪ TAPCON® 250
▪ TAPCON® 260
▪ TRAFOGUARD® with "Voltage regulation" options package
If you wish to operate several devices in parallel operation with existing de-
vices, you have to activate the TAPCON® 2xx retrofit function on each de-
vice.
Figure 132: Parallel operation of 2 devices with one TAPCON® 2xx. The TAPCON® 2xx retrofit
function must be active on both devices.