HES HART Device Status
HART device status messages are produced on the data being processed through the system
(i.e. data quality stamps, channel and field device status registers).
Field Device Status
The HES and field devices all produce a Field Device Status byte as defined by the HART
standard.
The field device status bytes are available on the ‘Field Device HART Status’ web page (see
figure 5.10) and can also be found in the MODBUS registers (see MODBUS registers section
for locations).
The HES Field Device Status byte is on the ‘HES HART Status and Variables’ Webpage and in
the MODBUS registers.
Table 6.11. MODBUS register 90067
Bit Name
HART definition
HES
specific
0
PV Outside
Limits
Primary Variable is beyond its operating limit.
N/A
1
Non PV
Outside Limits
A Device Variable not mapped to PV is beyond its
operating limit.
N/A
2
Loop Current
Saturated
The Loop Current has reached its upper (or lower)
endpoint limit and cannot increase (or decrease) and
further.
N/A
3
Loop Current
Fixed
The Loop Current is being held at a fixed value and is not
responding to process variations.
N/A
4
More Status
More status information is available via Command 48,
Read Additional Status Information
5
Cold Start
Cold Start – A power failure or Device Reset has
occurred
6
Configuration
Changed
An operation was performed that changed the device’s
configuration.
7
Device
Malfunction
The device detected a serious error or failure that
compromises HES device operation.
Additional Status
The HES and field devices all produce Additional Status bytes (25 maximum) as defined by the
HART standard.
If configured and available, the field device additional status bytes are on the ‘Field Device
HART Status’ webpage web page (see figure 5.10) and can also be found in the MODBUS
registers (see MODBUS registers section for locations).