HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[43]
Moore Industries-International, Inc.
o
Burst Mode
[off] - The HES supports enhanced broadcast messaging more
commonly referred to as burst mode for one field device per channel. When set
to burst mode, the field device will proactively send out messages instead of
waiting for the HART master to request them. This enables event driven
communication (high, low, deviation of signal or change in status) and/or timed
communication to the master. Burst slot is enabled when the user selects Burst
Mode. Select the Device number in the pull down menu.
NOTE:
The HART field device needs to be configured for Burst with the same burst
configuration (Command 3 or 9) as the HES.
•
Number of Retries
[1] – The number of times the HES will try a HART field device that
isn’t responding before declaring a communications error for that Field Device.
•
HART Devices – Channel X
o
Number of HART
Devices [1]
– the number of devices (up to 16) chosen on a
channel will equal the number of polling device addresses available (not grayed
out).
o
Device Y Polling Address
- This is the HART Polling Address for the selected
field device, enter a number from 0-63.