HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[69]
Moore Industries-International, Inc.
Table 5.2. HART Field Device Parameters
Parameter
Type
Group(s)
Base
Register
(b)
Group
size
(g)
No. of
registers
(r)
Register
Offset
(o)
Float Data
PV
float32
Float Dyn Vars A
1
8
2
0
SV
float32
Float Dyn Vars A
1
8
2
2
TV
float32
Float Dyn Vars A
1
8
2
4
QV
float32
Float Dyn Vars A
1
8
2
6
Loop Current
float32
Float Dyn Vars B
513
8
2
0
Device Variable 1
float32
Float Dev Vars
1025
16
2
0
Device Variable 2
float32
Float Dev Vars
1025
16
2
2
Device Variable 3
float32
Float Dev Vars
1025
16
2
4
Device Variable 4
float32
Float Dev Vars
1025
16
2
6
Device Variable 5
float32
Float Dev Vars
1025
16
2
8
Device Variable 6
float32
Float Dev Vars
1025
16
2
10
Device Variable 7
float32
Float Dev Vars
1025
16
2
12
Device Variable 8
float32
Float Dev Vars
1025
16
2
14
Integer Data
PV Integer
fixed point
Int Dyn Vars A
2049
4
1
0
SV Integer
fixed point
Int Dyn Vars A
2049
4
1
1
TV Integer
fixed point
Int Dyn Vars A
2049
4
1
2
QV Integer
fixed point
Int Dyn Vars A
2049
4
1
3
Loop Current Integer
fixed point
Int Dyn Vars B
2305
4
1
0
Device Variable 1
fixed point
Int Dev Vars
2561
8
1
0
Device Variable 2
fixed point
Int Dev Vars
2561
8
1
1
Device Variable 3
fixed point
Int Dev Vars
2561
8
1
2
Device Variable 4
fixed point
Int Dev Vars
2561
8
1
3
Device Variable 5
fixed point
Int Dev Vars
2561
8
1
4