HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[72]
Moore Industries-International, Inc.
Parameter
Type
Group(s)
Base
Register
(b)
Group
size (g)
No. of
registers
(r)
Register
Offset
(o)
Var6 Quality
unit8
Quality Dev Vars
3585
8
1
5
Var7 Quality
unit8
Quality Dev Vars
3585
8
1
6
Var8 Quality
unit8
Quality Dev Vars
3585
8
1
7
Status
Last HART Command
unit8
Status
4097
32
1
0
Response Code
unit8
Status
4097
32
1
1
Field Device Status
unit8
Status
4097
32
1
2
Configuration Change Counter
unit16
Status
4097
32
1
3
Additional Device Status
unit8
Status
4097
32
25
7
Field Device Configuration
PV, SV, TV & QV Units
unit8 array
Field Device
Config
6145
32
2
0
Loop Current Units
unit8
Field Device
Config
6145
32
1
2
Var1-8 Units
unit8 array
Field Device
Config
6145
32
4
4
Transmitter HART Revision
unit8
Field Device
Config
6145
32
1
15
PV Upper Range
float32
Field Device
Config
6145
32
2
16
PV Lower Range
float32
Field Device
Config
6145
32
2
18
Tag Bytes 0-7
ascii
Field Device
Config
6145
32
4
24
Manufacturing code
unit6
Field Device
Config
6145
32
1
28
Device Type code
unit16
Field Device
Config
6145
32
1
29
Field Device Serial Number
Unit24
Field Device
Config
6145
32
2
30