HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[48]
Moore Industries-International, Inc.
MODBUS/TCP Settings
1.
Select MODBUS
/
TCP in the selection pane
2.
Configure the various options, which control how Field Device data is placed in
MODBUS registers, and how errors are handled.
3.
Click “Apply”
Please remember to download to your device, refer to Saving the Configuration File to the HES
at the end of this section.
MODBUS Mapping Configuration
Allows the mapping of the HART field device variables to MODBUS registers. See Section 5 for
details on MODBUS Register definitions and HART field device registers.
Mapping Mode [By Variable Type]
•
By Variable Type
– Organize by Variable Type (Primary Variable1 (PV1), Primary
Variable 2 (PV2), Primary Variable 3 (PV3), etc.)
•
By Device Type
- Organize by Device Type (Primary Variable (PV1), Secondary
Variable (SV1), Tertiary Variable (TV1), Quaternary (QV1) etc.)