Moore Industries-International, Inc.
If you see a value of 0x000 press the F5 key on your keyboard to update the web page. When
you see the 0x001 value then your HES is successfully communicating with your MODBUS
Host via Ethernet (see Table 2.3).
Table 2.3. System Status Registers for Channel 1
Channel 1
Register Name
MB Reg
Value
Status
Ch 1 Consolidated
Status
9566
0x0010
(4) One or more Devices have Device
Malfunction Bit Set
Detected Devices
9569
0x0001
(0) Device 1 is Present
Devices Not
Producing Data
9571
0x0000
No status bits set
Now you can verify that HART data is passing from your HART device, through the HES, and
on to your MODBUS/TCP Host (even though your HART Field Device is not connected to your
process).
Go to the page entitled Field Device HART Status and observe the registers for Channel 1. You
should be able to see status information for Channel 1, Device 1 similar to the Table 2.4.
Table 2.4. Status Information for Channel 1, Device 1
Channel 1
Device
MB Reg
Status
Status Message
Channel 1, Device 1
Addr: 0
Tag: TAG4
4225
Field Device Status
(4) More Status
Available
(7) Device
Malfunction
4545
Additional Status
Not Read
Channel 1, Devices 2 to 16 are not polled.
Note that the Field Device Status in this example shows a code of (4) for More Status Available
and a code of (7) for Device Malfunction. This data is being transmitted by the HART Field
Device and is being successfully read by the HES. To ensure that this data is being
successfully passed along to your MODBUS/TCP Host you will have to use your MODBUS/TCP
Host to read Register 4225. Please see Figure 2.5 and notice that register 4225, bit position 4
shows a 1, and register 4225, bit position 7 also shows a 1. This proves that the HART data is
being successfully passed from your HART Field Device, through the HES, and on to your
MODBUS/TCP Host without error.