HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[6]
Moore Industries-International, Inc.
HES Quick Start Guide
The HES is ready to install and is set up either with your specified configuration or the default
configuration.
After programming your HES, Ethernet Gateway System, install the unit into your application
using the connection diagrams and terminal designation table located in this manual.
HART Input Settings:
For each HART input Primary Master, 1 HART Field Device with address 0, Normal
mode, 1 retry, polling with command 3, additional status off
Factory Default User Configuration for MODBUS:
Mapping = By variable
Compressed unused devices = OFF
Compressed CMD3/CMD9 Variables = OFF
Floating Point Word Order = Standard LSW
Number of Decimal Places = 0
Failed HART Device’s Register Value = Hold Last Value
HES System Settings:
ID tag=blank
Descriptor = blank
Message = blank
PV=DV66
SV=DV68
TV=DV70
QV=DV72
Network Default Configuration:
DHCP = ON
Name = HES
Location = TBD
MODBUS TCP connections = 4
HART-IP connections = 4
Security Jumpers Set To:
Network configuration = Read / Write
User configuration = Read / Write