Configuration Storage Error
Table 6.6. MODBUS register: 9514
Bit Name
What it Means
What to Do
0
Factory Data
Error
There was a problem reading the
factory information
Power cycle unit, if the error
returns then contact Moore
Industries Customer Support.
1
Network
Config Data
Error
There was a problem reading or
writing the network configuration
information
If this occurred after
reconfiguring the network
settings, reconfigure again and
power cycle the unit.
Otherwise contact Moore
Industries Customer Support.
2
User Data
Error
There was a problem reading or
writing the user configuration
information
If this occurred after
reconfiguring the user settings,
reconfigure again and power
cycle the unit.
Otherwise contact Moore
Industries Customer Support.
System Security Status
Table 6.7. MODBUS register: 9516
Bit Name
What it Means
What to Do
0
Network
Administration
Security Open
The Network Configuration Jumper is
in the enabled position. The
system's network properties including
IP Address can be reconfigured.
If security is required then set
network security jumper and
power cycle the unit.
1
User
Configuration
Security Open
The User Configuration Jumper is in
the enabled position. The system's
user configurable settings can be
reconfigured.
If security is required then set
user configuration jumper and
power cycle the unit.
2
RESERVED
3
Configuration
Default
Triggered
During power cycle, the
Configuration Default jumper was
detected, and the network
configuration was defaulted.
If this was unexpected then
contact Moore Industries
Customer Support.