HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[73]
Moore Industries-International, Inc.
HES HART data is always assigned to fixed registers 9001 through 9128.
Table 5.4. HES HART Data
Register
Type
No. of
registers
Parameter
Float Data
9001
float32
2
PV
9003
float32
2
SV
9005
float32
2
TV
9007
float32
2
QV
9017
float32
2
Var1
9019
float32
2
Var2
9021
float32
2
Var3
9023
float32
2
Var4
9025
float32
2
Var5
9027
float32
2
Var6
9029
float32
2
Var7
9031
float32
2
Var8
Integer Data
9033
fixed point
1
PV Integer
9034
fixed point
1
SV Integer
9035
fixed point
1
TV Integer
9036
fixed point
1
QV Integer
9041
fixed point
1
Var1 Integer
9042
fixed point
1
Var2 Integer
9043
fixed point
1
Var3 Integer
9044
fixed point
1
Var4 Integer
9045
fixed point
1
Var5 Integer
9046
fixed point
1
Var6 Integer
9047
fixed point
1
Var7 Integer