HES
User Manual
HART to Ethernet Gateway System
226-710-00A
September 2018
www.miinet.com
[83]
Moore Industries-International, Inc.
IO Channel Registers
Channel X Consolidated Status
Table 6.8. MODBUS register: 9566 (Channel 1); 9598 (Channel 2); 9630 (Channel 3); 9662
(Channel 4)
Bit Name
What it Means
What to Do
0
System Error
IO Channel has a system error.
Contact Moore Industries
Customer Support.
1
General Error
IO Channel has a general error.
Usually caused by No HART or
Partial Hart. See bits 2&3 below
or other channel status
registers.
2
No HART
Communications
None of the devices on this channel
have responded to command 0.
Check wiring / device
connections and field device
configuration (polling address).
3
Partial HART
Communications
At least one of the devices on this
channel is not responding to HART
commands.
See Devices registers to identify
problem device
4
Device
Malfunction Bit
Set
One or more devices on this channel
has its device malfunction bit set.
See field device HART registers
to identify the failed device and
address the issue.
5
Configuration
Change Bit Set
One or more devices on this channel
has its configuration changed bit set
See field device status registers
to identify the device and clear
the bit.
6
Channel
Disabled
This channel is configured to be
disabled
Information only. Reconfigure if
the channel is needed