6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
Related supplementary information
■
Permissible current of wire
The following table shows permissible currents of wire based on Table 28.1 of UL 508A and Table 40.3 of UL 508C.
The permissible current values listed in this table are for when the number of wires bundled is three or less. When the number
of wires bundled is four to six, the permissible current values are 80 % of the values in the table.
• Permissible currents of copper wire (insulated conductor)
■
Rated input current of servo amplifier
The following table shows the 3-phase rated input currents and maximum wire sizes for the MR-J5 series.
• 3-phase rated input currents, inrush currents, and maximum wire sizes for servo amplifiers
■
Molded-case circuit breakers (MCCB) and magnetic contactors (MC)
The following tables show lists of rated currents for the Mitsubishi Electric UL 489 Listed molded-case circuit breakers and for
magnetic contactors.
• List of rated currents for molded-case circuit breakers (MCCB)
*1 For molded-case circuit breakers that support the current values enclosed in brackets "( )" in the rated current column, contact your local
sales office.
• List of rated currents for magnetic contactors (MC)
Wire size
60 °C (140 °F)
75 °C (167 °F)
AWG
Actual cross-sectional
area [mm
2
]
Nominal cross-
sectional area [mm
2
]
[A]
[A]
14
2.1
2
15
15
12
3.3
3.5
20
20
10
5.3
5.5
30
30
8
8.4
8
40
50
6
13.3
14
55
65
4
21.2
22
70
85
2
33.6
38
95
115
1
42.4
110
130
Model
Input current [A]
Inrush current [A]
Maximum AWG
MR-J5-10_
0.9
17
14
MR-J5-20_
1.5
17
14
MR-J5-40_
2.6
17
14
MR-J5-60_
3.2
17
14
MR-J5-70_
3.8
17
14
MR-J5-100_
5
17
14
MR-J5-200_
10.5
24
14
MR-J5-350_
16
85
12
MR-J5-500_
21.7
42
10
MR-J5-700_
28.9
85
8
MR-J5W2-22G_
2.9
23
14
MR-J5W2-44G_
5.2
23
14
MR-J5W3-222G_
4.3
23
14
MR-J5W3-444G_
7.8
23
14
MR-J5W2-77G_
7.5
36
14
MR-J5W2-1010G_
9.8
36
14
Model
Rated voltage AC [V]
Rated current [A]
NF125-SVU
480
15, 20, 30, 40, 50, 60, (70), 75, (80), (90), 100, 125
MS-T series
Frame
T10
T12
T20
T21
T25
N35
N50
N65
N80
N125
AC3 class [kW/A]
220 V
2.2
2.7
3.7
4
5.5
7.5
11
15
19
30
440 V
2.7
4
7.5
7.5
11
15
22
30
37
60
Thermal current [A]
20
20
20
32
32
60
80
100
120
150