224
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.15 Earth-leakage current breaker
MR-J5W_-_G_
Rated sensitivity current
≥
10 • {Ig1 + Ign + Iga + K • (Ig2 (A-axis) + Igm (A-axis) + Ig2 (B-axis) + Igm (B-axis) + Ig2 (C-axis) +
Igm (C-axis))} [mA] . . . (6.2)
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input terminals of the servo
amplifier
Page 225 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo motor
Page 225 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF(-H))
Iga: Servo amplifier leakage current
Page 225 Servo amplifier leakage current example (Iga)
Igm: Servo motor leakage current
Page 225 Servo motor leakage current example (Igm)
Earth-leakage current breaker
K
Type
Mitsubishi Electric products
Models provided with harmonic and surge reduction
techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
1
General models
BV-C1
NFB
NV-L
3
Ign
Ig1
Iga
Ig2
Igm
Ig2
Igm
Ig2
Igm
M
NV
M
M
Cable
A-axis
Cable
Noise filter
Cable
Servo
amplifier
B-axis
Cable
C-axis