6 OPTIONS AND PERIPHERAL EQUIPMENT
6.14 Noise reduction techniques
219
6
■
Surge killer (recommended)
Use of a surge killer is recommended for AC relay, magnetic contactor or the like near the servo amplifier. Use the following
surge killer or equivalent.
Ex.
CR-50500 (Okaya Electric Industries)
Note that a diode should be installed to a DC relay or the like.
Maximum voltage: Not less than four times the drive voltage of the relay or the like
Maximum current: Not less than two times the drive current of the relay or the like
■
Cable clamp fitting AERSBAN-_SET
Generally, connecting the grounding wire of the shielded wire to the SD terminal of the connector provides a sufficient effect.
However, the effect can be increased when the shielded wire is connected directly to the ground plate as shown below.
Install the ground plate near the servo amplifier for the encoder cable. Peel part of the cable insulator to expose the external
conductor, and press that part against the ground plate with the cable clamp. If the cable is thin, clamp several cables in a
bunch.
The cable clamp comes as a set with the grounding plate.
[Unit: mm]
Rated
voltage
AC [V]
C [
μ
F
±20 %]
R [
Ω
±30
%]
Test voltage
Dimensions [Unit: mm]
250
0.5
50 (1/2W)
Between
terminals: 625
V AC, 50 Hz/60
Hz 60 s
Between
terminal and
case: 2000 V
AC
50/60 Hz 60 s
MC
SK
MC
OFF
ON
Relay
Surge killer
Surge killer
20 cm or less
φ
(18.5 + 2) ± 1
6 ± 1
15 ± 1
48 ± 1.5
6 ± 1
16 ± 1
φ
3.6
Mounting band
AWG 18 stranded wire
Soldered
300 or more
300 or more
(18.5 + 5) or less
-
+
RA
Diode
40
Strip the cable insulator
of the clamped area.
Cutter
Cable
Clamp fittings
(A, B)
Grounding plate
Cable
External conductor
Clamp section diagram
Содержание Melservo-J5 MR-J5 Series
Страница 1: ...MR J5 User s Manual Hardware MR J5 _G_ MR J5W_ _G_ MR J5 _A_ Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 441: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 439 12 MEMO ...
Страница 445: ......