186
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.4 FR-XC multifunction regeneration converter
Connection diagram
200 V class
*1 Configure a sequence that shuts off the main circuit power supply in the following situations:
When an FR-XC or servo amplifier alarm occurs.
When EM1 (Forced stop 1) is enabled.
*2 Configure a sequence that shifts the status to servo-on once the FR-XC is ready.
*3 Ensure that the servo motor stops by using a forced stop input to the controller when an alarm occurs in the FR-XC. If the controller does
not have an emergency stop input, use the forced stop input of the servo amplifier to stop the servo motor.
*4 When using the FR-XC, remove the wire between P3 and P4.
*5 To use EM1 (Forced stop 1), set [Pr. PA04.3] and [Pr. PA04.2] to "0".
*6 If wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
*7 Although the diagram shows the input signal and the output signal each using a separate 24 V DC power supply for illustrative purposes,
the system can be configured to use a single 24 V DC power supply.
*8 Remove the R1/L11 and S1/L21 jumpers when using a dedicated power supply for the control circuit.
*9 Do not connect anything to the P4 terminal of the FR-XC.
*10 Install a fuse on each wire between the FR-XC and servo amplifier.
*11 Wire the built-in regenerative resistor when using servo amplifiers with a capacity of 7 kW or less. (factory-wired).
*12 The inputs/outputs (main circuit) of the FR-XC and servo amplifier contain high-frequency components which may interfere with the
signals of peripheral communication equipment. Installing a radio noise filter (FR-BIF) or line noise filter (FR-BSF01 and FR-BLF) can
help reduce the effects of signal interference.
*13 When connecting a DC power supply between the FR-XC and servo amplifier, use twisted wire and with total length of 5 m or less.
*14 Install a dedicated stand-alone reactor (FR-XCL) when using the FR-XC. Do not use a power factor improving AC reactor (FR-HAL) or
power factor improving DC reactor (FR-HEL).
Page 184 Dedicated stand-alone reactor
T/L3
S/L2
R/L1
T2/L32
MC
MCCB
S2/L22
R2/L12
FR-XCL
*14
MC
RA2
RA1
EM1
*1
MC
SK
RA1
*3
EM1
R2/L12
S2/L22
N/-
P4
*9
*2
RYB
RYA
SE
P/+
T2/L32
R/L1
S/L2
T/L3
*1
L11
L21
*10
P4
N-
U
V
W
EM1
*1*5
R1/L11
S1/L21
*8
U
V
W
E
CN2
FR-XC
*4
*6
DICOM
B
C
A
RA1
DOCOM
ALM
RA2
*13
3-phase
200 V AC
to 240 V AC
OFF
ON
Servo motor
Servo amplifier
*11*12
Controller
24 V DC
*7
24 V DC
*7
24 V DC
*7
Содержание Melservo-J5 MR-J5 Series
Страница 1: ...MR J5 User s Manual Hardware MR J5 _G_ MR J5W_ _G_ MR J5 _A_ Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 441: ...12 USING A FULLY CLOSED LOOP SYSTEM 12 7 Absolute position detection system 439 12 MEMO ...
Страница 445: ......