39
Function list
Fu
nc
tio
ns
Lis
t
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
rPM
A109
[Motor RPM]
Displays the number of Motor RPM.
-
-
dCL
A10A
[Inverter DC
link voltage]
Displays DC link voltage inside the
inverter.
-
-
vOL
A10B
[User display
select]
This parameter displays the item selected
at H73- [Monitoring item select].
vOL
-
vOL
Output voltage
POr
Output power
tOr
Torque
nOn
A10C
[Fault Display]
Displays the types of faults, frequency
and operating status at the time of the
fault
-
-
drC
A10D
[Direction of
motor rotation
select]
F, r
Sets the direction of motor rotation when
drv - [Drive mode] is set to either 0 or 1.
F
O
F
Forward
r
Reverse
drv2
A10E
[Drive
mode 2]
0 - 3
0
Run/Stop via Run/Stop key on the
keypad
1
X
1
Terminal
operation
FX: Motor forward run
RX: Motor reverse run
2
FX: Run/Stop enable
RX: Reverse rotation select
3 RS-485 communication
Frq2
1)
A10F
[Frequency
setting
method 2]
0 - 8
0
Digital
Keypad setting 1
0
X
1
Keypad setting 2
2
Analog
V1 1: -10 - +10 [V]
3
V1 2: 0 - +10 [V]
4
Terminal I: 0 - 20 [mA]
5
Terminal V1 setting 1 +
Terminal I
6
Terminal V1 setting 2+
Terminal I
7 RS485 communication
8 Digital Volume
rEF
2)
A110
PID control
standard
value setting
0-400
[Hz] or
0-100
[%]
If H58 is 0, it is expressed as a [Hz] unit.
If H58 is 1, it is expressed as a [%] unit.
In [Hz] unit, you can
’t set Max.
frequency more than (F21).
In [%] unit, 100% means Max.
frequency.
0.00
O
Fbk
2)
A111
PID control
feedback
amount
It indicates a feedback amount in PID
control.
If H58 is 0, it is expressed as a [Hz] unit.
If H58 is 1, it is expressed as a [%] unit.
-
-
1)
Only displayed when one of the Multi-function input terminals 1-4 [I17-I20] is set to
“22”.
2)
It is indicated when H49(PID control selection) is 1.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...