Advanced functions
134
8.26 2 Phase PWM Operation
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function Group 2
H48
PWM controlling mode
0: NORMAL PWM
1: 2 phase PWM
1
0 - 2
0
►
Heat loss and leakage current from inverter can be reduced when H48 is set to 1(2
phase PWM) according to the ratio of load.
8.27 Cooling fan control
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 2
H77
[Cooling Fan Control] -
0 - 2
0
►
Control the On/ Off of the cooling fan to cool the Inverter heatsink.
►
When it is set to 0:
- Cooling fan begins to operate when power ON.
- Cooling fan is stopped when inverter main circuit voltage becomes low voltage due to
power off.
►
When it is set to 1:
- Cooling fan begins to operate when power is turned ON with operating command ON.
- Cooling fan is stopped when operating command is turned Off with inverter output
shut off.
- Cooling fan keeps operating when heat sink temperature exceeds a certain limit
regardless of operating command.
- Used when frequent Run/Stop or quite stop is required. This may make the cooling
fan life longer.
►
When it is set to 2:
- The cooling fan is not active even when power is supplied to the inverter and an
operating command is input. However, if the temperature of the inverter heat sink is
higher than a certain degree, cooling fan is active.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...