Monitoring
154
8: Over voltage trip (Ovt)
►
Activated when over voltage trip occurs due to DC link voltage exceeded 400Vdc for
200V class and 820Vdc for 400V class.
9: Low voltage trip (Lvt)
►
Activated when low voltage trip occurs due to DC link voltage under 180Vdc for 200V
class and 360Vdc for 400V class.
10: Inverter heatsink overheat (OHt)
►
Activated when the heatsink is overheated.
11: Command loss
►
Activated when Analog (V1,I) and RS485 communication commands are lost.
12: During operation
►
Activated when run command is input and inverter outputs its voltage.