Keypad
display
Protective
functions
Descriptions
Operating
method when
the frequency
command is lost
When inverter operation is set via Analog input (0-10V or 0-
20mA input) or option (RS485) and no signal is applied,
operation is done according to the method set in I62
(Operating method when the frequency reference is lost).
NTC open
When NTC is not connected, outputs are cut off.
12.2 Fault remedy
Keypad display
Cause
Remedy
Overcurrent
When an overcurrent fault occurs, operation must be started after the cause
is removed to avoid damage to IGBT inside the inverter.
Accel/Decel time is too short compared
to the GD
²
of the load.
Load is greater than the inverter rating.
Inverter output is issued when the
motor is free running.
Output short circuit or ground fault has
occurred.
Mechanical brake of the motor is
operating too fast.
Increase the Accel/Decel time.
Replace the inverter with
appropriate capacity.
Resume operation after stopping
the motor or use H22 (Speed
search).
Check output wiring.
Check the mechanical brake.
Ground fault
current
Ground fault has occurred at the output
wiring of the inverter
The insulation of the motor is damaged
due to heat
Check the wiring of the output
terminal.
Replace the motor.
Inverter
overload
Load is greater than the inverter rating.
Torque boost scale is set too large.
Upgrade the capacity of motor
and inverter or reduce the load
weight.
Reduce torque boost scale.
Overload trip
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...