RS485 communication
175
Com
mu
nica
tion
11.2 Specification
Item
Specification
Communication method
RS485
Transmission form
Bus method, Multi drop Link System
Applicable inverter
SV-iG5H series
Converter
RS232 converter
Connectable drives
Max 16
Transmission distance
Max. 1,200m (Within 700m Recommend)
Communication speed
19,200/9,600/4,800/2,400/1,200 bps selectable
Control procedure
Asynchronous communication system
Communication system
Half duplex system
Character system
ASCII (8 bit)
Stop bit length
Modbus-RTU: 2 bit LS Bus: 1 bit
Sum check
2 byte
Parity check
None
Installation
Use S+, S- terminals on control terminal block
Power supply
Use Insulated power from the inverter power supply
11.3 Installation
Connecting the communication line
Connect the RS-485 communication line to the inverter
’s (S+), (S-) terminals of the control
terminals.
Check the connection and turn ON the inverter.
If the communication line is connected correctly set the communication-related parameters
as the following:
DRV-03 [Drive mode]: 3(RS485)
DRV-04 [Freq. mode]: 7(RS485)
I/O-60 [Inv. Number]: 1-250 (If more than 1 inverters are connected, be sure to use
different numbers for each inverter)
I/O-61 [Baud-rate]: 3 (9,600 bps as Factory default)
I/O-62 [Lost Mode]: 0 - No action (Factory default)
I/O-63 [Time-Out]: 1.0 sec (Factory default)
I/O-59 [Comm. Prot]: 0 - Modbus-RTU, 1
– LS BUS
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...