Advanced functions
136
8.29 Accel/Decel Change Frequency
This function is to use a different ACC/DEC time starting from a set frequency.
At start, up to A37_Start&End Ramp frequency, the motor accelerates a normal time
and from A37 frequency, ACC time references A35_StartRampAcc.
During decel stop, A36_EndRampAcc is referenced until A37 frequency and normal
deceleration time is applied.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Application
Group
A35
StartRampAcc
-
-0-6000
10.0
sec
A36
EndRampDec
-
-0-6000
10.0
sec
A37
Start&End Ramp
-
-0-Max Freq.
0.00
sec
•
The inverter operates at the slope set at A35, A36 below the Start&End Ramp
frequency set at A37 of the operating frequency. However, if the operating
frequency rises over the Start&End Ramp, the inverter runs at the Acc/Dec slope
set at ACC, DEC in the drive group.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...