Advanced functions
103
A
dv
an
ce
d
Fu
nc
tio
ns
8.4 3-Wire
Group
Code
Parameter Name
Setting Range
Default
Unit
I/O group
I17
[Multi-function Input terminal P1
select]
0
0 - 30
0
-
-
I20
[Multi-function Input terminal
P4 select]
17
3
Select the terminal from P1-P4 for use as 3-Wire operation.
If P4 is selected, set I20 to 17 {3-Wire operation}.
Input signal is latched (saved) in 3-Wire operation. Therefore, inverter can be operated
by Push-button switch.
The bandwidth of pulse (t) should not be less than 50msec.