51
Function list
Fu
nc
tio
ns
Lis
t
Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H50
1)
A332
[PID F/B
select]
0 - 2
0 Terminal I input (0 - 20 mA)
0
X
1 Terminal V1 input (0 - 10 V)
2 RS-485 communication feedback
H51
A333
[P gain for PID]
0-
999.9
[%]
This parameter sets the gains for the PID
controller.
300.0
O
H52
A334
[Integral time
for PID
0.1-
32.0
[sec]
1.0
O
H53
A335
[Differential
time for PID (D
gain)]
0 -
30.0
[sec]
0.0
O
H54
A336
[PID control
mode select]
0-1
Selects PID control mode
0
X
0 Normal PID control
1 Process PID control
H55
A337
[PID output
frequency high
limit]
0.1 -
400
[Hz]
This parameter limits the amount of the
output frequency through the PID control.
The value is settable within the range of
F21
– [Max frequency] and F23 – [Start
frequency].
50.00
O
H56
A338
[PID output
frequency low
limit]
0.1 -
400
[Hz]
0.50
O
H57
A339
[PID standard
value select]
0-4
Selects PID standard value.
Standard value is indicated in “rEF” of
Drive group.
0
X
0 Loader digital setting 1
1 Loader digital setting 2
2 V1 terminal setting 2: 0-10V
3 I terminal setting: 0-20mA
4 Setting as a RS-485 communication
H58
A33A
PID control unit
select
0-1
Selects a unit of the standard value or
feedback amount.
1
X
0 Frequency[Hz]
1 Percentage[%]
H59
A33B
PID Output
Inverse
0 - 1
Select the output direction of PID control.
0
X
0 No
1 Yes
H60
A33C
PID Step Ref1
0-100
[%]
Sets the PID Step1 Reference Percent.
30.0
O
H61
A33D
PID Step Ref2
0-100
[%]
Sets the PID Step2 Reference Percent.
25.0
O
H62
A33E
PID Step Ref3
0-100
[%]
Sets the PID Step3 Reference Percent.
20.0
O
1)
Set H49 to 1 (PID control) to display this parameter.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...