Advanced functions
99
A
dv
an
ce
d
Fu
nc
tio
ns
Terminal JOG FX/RX operation
8.2.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F20
[Jog frequency]
-
0 - 400
10.00
Hz
I/O group
I19
[Multi-function input terminal
P3 define]
26
0 - 30
2
I20
[Multi-function input terminal
P4 define]
27
0 - 30
3
Set the desired jog frequency in F20.
Select a terminal from P1
– P4 to use for this setting.
If P3 is set for Jog operation, set I19 to 26 {Jog}.
►
Jog
frequency‘s setting range can be set between Max. frequency (F21) and start
frequency (F23).
►
The following diagram is an example when reference frequency is 30Hz and Jog
frequency is 10 Hz.