53
Function list
Fu
nc
tio
ns
Lis
t
Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H77
1)
A34D
[Cooling fan
control]
0 - 2
0 Always ON
0
O
1
Keeps ON when its temp is higher
than inverter protection limit temp.
Activated only during operation when
its temp is below that of inverter
protection limit.
2
Regardless of the operation fan is
active when its temp is higher than
inverter protection limit temp.
H78
A34E
[Operating
method select
when cooling fan
malfunctions]
0 - 1
0
Continuous operation when cooling
fan malfunctions.
0
O
1
Operation stopped when cooling fan
malfunctions.
H79
A34F
[S/W version]
x.xx
This parameter displays the inverter
software version.
x.xx
X
-
H81
2)
A351
[2nd motor
Accel time]
0 -
6000
[sec]
This parameter actives when the
selected terminal is ON after I17-I20 is
set to 12 {2nd motor select}.
5.0
O
H82
A352
[2nd motor
Decel time]
10.0
O
H83
A353
[2nd motor
base
frequency]
30 -
400
[Hz]
50.00
X
H84
A354
[2nd motor V/F
pattern]
0 - 2
0
X
H85
A355
[2nd motor
forward torque
boost]
0 -
15 [%]
5
X
H86
A356
[2nd motor
reverse torque
boost]
5
X
H87
A357
[2nd motor stall
prevention
level]
30-
150
[%]
130
X
H88
A358
[2nd motor
Electronic
thermal level
for 1 min]
50-
200
[%]
120
O
H89
A359
[2nd motor
Electronic
thermal level
for continuous]
50-
150
[%]
100
O
H90
A35A
[2nd motor
rated current]
0.1-
100 [A]
26.3
X
1)
Exception: Since SV004iG5H-2/SV004iG5H-4 is Natural convection type, this code is hidden.
2)
It is indicated when choosing I17-I20 as a 12 (2nd motor select).
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...