Protective functions
173
Pro
tec
tiv
e
Fu
nc
tio
ns
►
A40: Sets the detection delay time.
►
A41: Sets the Pipe Broken frequency.
►
I54-55: Relay output in case of Pipe Broken
10.12 Over Pressure
Over Pressures used to prevent accidents that may arise through high feedback.
Trip occurs if the feedback of the PID is higher than the A63_Over Pressure level.
In Auto configuration in A62_Over Pressure Trip, automatic reset and restart will be
performed after feedback decline to Wake-up Level.
►
A62: If set to 1 (Auto), auto-Reset / Restart will be performed automatically after
reaching the Wake-up Level. If set to 2 (Manual), it have to be reset manually.
►
A63: Defines the Over Pressure level.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Application
group
A62
Over Pressure Trip
-
0: None
1: Auto
2: Manual
0
A63
Over Pressure Lvl
-
0-100.0
80.0
%
I/O group
I54-55
Relay Define x
-
21. Over
Pressure
Application
group
A6
Wake-up Level
-
0-100.0
20.0
%
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...