Advanced functions
100
8.3 UP-DOWN Operation
Up-down storage function
8.3.1
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive
group
Frq
[Frequency setting method]
8
0-8
0
I/O group
I17
[Multi-function input terminal P1
define]
0
0 - 30
0
I18
[Multi-function input terminal P2
define]
25
1
I19
[Multi-function input terminal
P3define]
15
2
I20
[Multi-function input terminal
P4define]
16
3
Function
group 1
F63
[Up-down frequency Save select] -
0-1
0
F64
[Up-down frequency storage]
-
0.00
Select 8 in Frq code of drive group
Select the terminal which uses as a up-down drive among multi-function input (P1-P4)
If you select P3 and P4 as an up-down drive terminal, select each 15 (frequency
increase command) and 16 (frequency decrease command) in the I19 and I20 of I/O
group.
If you select P2 terminal as an up-own save initial terminal, select 25 (up-down save
initialization) as above.
Up/down Save function: If F63, ‘Save up/down frequency’, is set to 1, the frequency
before the inverter was stopped or decelerated is saved in F64.
►
While up-down save operates, the user can initialize the saved up-down frequency by
setting multi-function input terminal as a up-down frequency save initialization.
F63 Save up/down frequency select
0 Remove
‘save up/down frequency’
1 Set
‘save up/down frequency’
F64 Save up/down frequency
Up/down frequency saved
►
If
‘Up/Down Save Frequency Initialization’ signal is input while the multi-function input
‘Up’ or ‘Down’ function is applied, this signal is ignored.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...