75
Basic Functions
B
as
ic
Fu
nc
tio
ns
►
Wire the terminals as shown below and refer to I 6 - I 10.
Frequency setting via 0 - 20 [mA] input
7.1.5
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive
group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
4
0 - 8
0
I/O
group
I11
[Filter time constant for I input]
10
0 - 9999
10
I12
[I input minimum current]
-
0 - 20
4
mA
I13
[Frequency corresponding to I12] -
0 - 400
0.00
Hz
I14
[I input max current]
-
0 - 20
20
mA
I15
[Frequency corresponding to I14] -
0 - 400
60.00
Hz
Select 4 in Frq code of Drive group.
Frequency is set via 0-20mA input between I and CM terminal.
Frequency setting via -10 - +10[V] voltage input + 0 -
7.1.6
20[mA] input
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive
group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
5
0 - 8
0
Select 5 in Frq code of Drive group.
Override function available using Main/Auxiliary speed adjustment
Related code: I 2 - I 5, I 6 - I10, I11 - I15
►
Override function is to gain precise control and fast response by combining Main and
Auxiliary speed input. Fast response can be achieved by Main speed and precise
control can be accomplished by Aux. speed if the accuracy of Main/Aux speed is set
differently.
►
Follow the setting below when Main speed is given via 0 - 20mA with Aux. speed via V1
terminal (
–10 - 10V).
►
When override function is used, select the Main/Aux. speed according to loads used.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...