Protective functions
159
Pro
tec
tiv
e
Fu
nc
tio
ns
10 Protective functions
10.1 Electronic Thermal
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F50
[ETH (Electronic thermal)
select]
1
0 - 1
0
F51
[Electronic thermal level for 1
minute]
-
50 - 200 120
%
F52
[Electronic thermal level for
continuous]
-
50 - 150 100
%
F53
[Motor type]
-
0 - 1
0
Select F50
– [Electronic thermal select] to 1.
It activates when the motor is overheated (time-inverse). If current greater than set in
F51 flows, inverter output is turned off for the preset time in F51- [Electronic thermal
level for 1 minute].
►
F51: Enter the value of max current that is capable of flowing to the motor continuously
for one minute. It is set in percent of motor rated current. The value cannot be set lower
than F52.
►
F52: Enter the amount of current for continuous operation. Normally motor rated current
is used. It cannot be set greater than F51.
►
F53: For an inductance motor, cooling effects decrease when a motor is running at low
speed. A special motor is a motor that uses a separately powered cooling fan maximize
cooling effect even in low speed.
F53
[Motor type]
0
Standard motors having a cooling fan directly
connected to the shaft
1
Special motor that uses a separately powered cooling
fan.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...