
Advanced functions
132
8.25 DRAW Operation
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
Group 1
F70
DRAW mode select -
0 - 3
0
-
F71
DRAW ratio
-
0.0 - 100.0
0.0
%
►
It
’s a kind of open loop tension control that uses the speed difference of motor running
under main frequency command to keep material
’s tension in between steady.
►
The ratio reflected in the output frequency differs according to the selection of
F70(DRAW mode select)
F70
Draw
Operation
0
Draw not operated
1
V1(0-10V) input draw operation
2
I(0-20mA) input draw operation
3
V1(-10-10V) input draw operation
►
Select 1 and 2 for F70
The center value of analogue input (selected by the set value of I6-I15) as standard, if
the input is big it gets (+), if small (-) and gets reflected in the output frequency as the
ratio set in F71.
►
Select 3 for F70
OV as standard, if analog input voltage is big, it gets (+), if small (-) and gets reflected in
the output frequency as the ratio set in F71.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...