Protective functions
161
Pro
tec
tiv
e
Fu
nc
tio
ns
10.2 Overload Warning and trip
Overload warning
10.2.1
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F54
[Overload warning level]
-
30 - 150
110
%
F55
[Overload warning time]
-
0 - 30
10
Sec
I/O group
I54
[Multi-function relay1 select] 5
0 - 27
12
I55
[Multi-function relay2 select]
5
17
Select one output terminal for this function between Relay1 and Relay2.
If selecting Relay1 as output terminal, set I54 to 5 {Overload: OL}
►
F54: Set the value as a percent of motor rated current.
Overload trip
10.2.2
Group
Code
Parameter
Set
Range
Default
Unit
Function
group 1
F56
[Overload trip select]
1
0 - 1
1
F57
[Overload trip level]
-
30 - 200
120
%
F58
[Overload trip time]
-
0 - 60
60
sec
Set F56 to 1.
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when excessive current flows to the motor for F58
–
[Overload trip time].
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...