41
Function list
Fu
nc
tio
ns
Lis
t
Function group 1
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
F21
A215
[Max
frequency]
40 -
400
[Hz]
This parameter sets the highest frequency
the inverter can output.
It is frequency reference for Accel/Decel
(See H70)
Any frequency cannot be set above
Max frequency except Base frequency
50.00
X
F22
A216
[Base
frequency]
30 -
400
[Hz]
The inverter outputs its rated voltage to
the motor at this frequency (see motor
nameplate).
50.00
X
F23
A217
[Start
frequency]
0.1 -
10
[Hz]
The inverter starts to output its voltage at
this frequency.
It is the frequency low limit.
0.50
X
F24
A218
[Frequency
high/low limit
select]
0 - 1
This parameter sets high and low limit of
run frequency.
0
X
F25
1)
A219
[Frequency
high limit]
0 -
400
[Hz]
This parameter sets high limit of the run
frequency.
It cannot be set above F21
– [Max
frequency].
50.00
X
F26
1)
A21A
[Frequency
low limit]
0 -
400
[Hz]
This parameter sets low limit of the run
frequency.
It cannot be set above F25 - [Frequency
high limit] and below F23
– [Start
frequency].
0.50
X
F27
A21B
[Torque Boost
select]
0 - 1
0 Manual torque boost
0
X
1 Auto torque boost
F28
A21C
[Torque boost
in forward
direction]
0 - 15
[%]
This parameter sets the amount of torque
boost applied to a motor during forward
run.
It is set in percent of Max output voltage.
4.0
X
F29
A21D
[Torque boost
in reverse
direction]
This parameter sets the amount of torque
boost applied to a motor during reverse
run.
It is set as a percent of Max output voltage
4.0
X
1)
Only displayed when F24 (Frequency high/low limit select) is set to 1.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...