Advanced functions
128
►
Used when an inverter operates 2 motors connected to two different types of the loads.
►
2
nd
motor operation does not drive 2 motors at the same time.
►
As the figure below, when using two motors with an inverter by exchanging them, select
one motor from 2 motors connected. When 1
st
selected motor operation is stopped,
select a terminal for 2
nd
motor and define H81-H90 parameters to drive the 2
nd
motor.
►
Define the 2nd motor select when a motor is stopped.
►
H81 - H90 parameters function the same as 1
st
motor.
8.23 Frequency setting and 2
nd
drive method select
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive
group
drv
Drive mode 1
-
0 - 3
1
-
Frq
Frequency mode 1
-
0 - 8
0
-
drv2
Drive mode 2
-
0 - 3
1
Frq2
Frequency mode 2
-
0 - 8
0
I/O group
I17-I20
Multi-function input terminal
P1 select
22
0 - 30
Drive mode 1 is used when the input set as 2
nd
source is not entered into multi-input
(I17-I20)
Drive mode 2 can input frequency setting and drive command as a 2
nd
setting value by
using multi-input terminal. In case of driving away from inverter by communication, it is
used when quit the communication and operate by inverter.
The switching method for Drive mode 1 and Drive mode 2 is as follows
If multi-input terminal set as Drive mode 2 is off, it used as Drive mode 1. If multi-input
terminal set as Drive mode 2 is on, it used as Drive mode2.
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...