Chapter 6 - Parameter Description [APP]
145
6.6 Application Group [APP]
APP-00: Jump to desired code #
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.
APP-01: Application Mode Selection
This code sets the application mode.
Setting Range
LCD
7-Seg
Description
None
0
Application mode is not selected.
Traverse
1
Traverse mode is selected in application
group. Related functions (APP-02~07)
are displayed.
MMC
2
MMC (Multi-Motor Control) mode is
selected in application group. Related
functions (APP-08~31) are displayed.
DRAW
3
DRAW mode is selected in application
group. Related functions (APP-32~33)
are displayed.
[Traverse]:
This is a mechanism to wind thread to an
intended shape on a reel with a rotary motion and
reciprocation. Adjusting the speed of mechanical
reciprocation can make different shapes of thread reel.
The following figure shows an example. The guide
should move with low speed at the center of the reel and
fast at the edge of the reel.
[An example of Traverse Operation]
[Traverse Operation Pattern]
[MMC]:
The ‘PID’ control should be selected in FU2-47
to use this function.
♦
One inverter can control multiple motors. This function
is often used when controlling the amount and pressure
of flow in fans or pumps. Built-in PI controller controls a
main motor after receiving process control value and
keeps the control value constant by connecting auxiliary
motors to commercial line when needed.
♦
In case that flow amount or flow pressure is beyond or
below the reference so the main drive cannot control by
itself, auxiliary motors are automatically turned on/off.
Maximum four (Q1~3 and Aux. output) auxiliary motors
can be run. Each Starting and Stop Frequency should
be set to four auxiliary motors.
♦
Auto Change can be selected to automatically switch
the order of the running motors for keeping motor run-
time constant. Set mode ‘1’ for automatic changing of
auxiliary motors only and set mode ‘2’ for automatic
changing of all motors including main motor. For m ode
‘2’, external sequence (Refer to APP-26) should be
configured.
APP? Jump code
00 1
Factory Default:
1
APP? App. mode
01 None
0
01
Factory Default:
None
0
Traverse
Rotary
Motion
Thread
Traverse
Reciprocation
(Mechanical)
Thread
(Constant
Speed)
APP-05
Traverse Dec
APP-03
Trv. Scr
APP-04
Traverse Acc
APP-06
Offset-High
APP-07
Offset-Low
Reference
Speed
APP-02
Trv. Amp
Related Functions:
APP-02 to APP-07 [Traverse Parameters]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-30 to EXT-32 [Multi-Function Output]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]