Chapter 4 – Quick start procedures
55
4.3.2
Frequency set by Keypad and Run/Stop by External Source.
1.
Connect wiring as shown below.
2.
Apply AC power.
3.
Confirm that the DRV 03 is set at ‘Fx/Rx-1’.
4.
Confirm that the DRV 04 is set at
‘Keypad-1’.
5.
Press
[SHIFT/ESC]
key.
6.
LCD:
Press
[PROG]
key.
7-Seg:
Press
[PROG/ENT]
key.
7.
LCD:
Set the frequency using
[SHIFT/ESC]
and
[
?
]
key.
7-Seg:
Set the frequency by rotating the
encoder knob.
8.
LCD:
Press
[ENT]
key to save the data.
7-Seg:
Press [
PROG/ENT]
key to save the
data.
9.
Close the FX or RX contact to run the motor.
10. Open the FX or RX contact to stop the
motor.
LCD Display
7-Segment Display
P1 P2
JOG
CM
P3 FX RX NC
CM BX
RST
I
VR VI
FM 5G
DRV?T/K 0.0 A
00 STP 0.00Hz
DRV? Drive mode
03 Fx/Rx-1
DRV? Freq mode
04 Keypad-1
DRV?T/K 0.0 A
00 STP 0.00Hz
DRV? Cmd. freq
00 0.00Hz
DRV?T/V 0.0 A
00 STP 60.00Hz
The FWD or REV LED starts blinking.
DRV? Cmd. freq
00 60.00Hz
The FWD or REV LED starts blinking.
The DRV LED is ON.
The PROG/ENT LED is turned ON.
The PROG/ENT LED is turned ON.
The RUN LED starts blinking.
The RUN LED starts blinking.