Chapter 7 - Options
164
7.4.3
RS485 & MODBUS-RTU Communication
[Performance Specification]
Category
Specification
Communication Method
RS485 (RS232-485 Converter)
Transmi ssion Form
Bus method Multi-drop Link System
Applicable Inverter
SV-iS5 series
Converter
Converter equipped with RS232
Number of connectable Inverter
31, Max.
Transmission Distance
Max. 1200m (Within 700m is desired)
[Hardware Specification]
Category
Specification
Installation
Install on the Control Board of Inverter using option connector (CN2)
Control Board
Powered by Inverter
Power
Supply
Communication Board
Powered by Control Board Power (Isolated Power)
[Communication Specification]
Category
Specification
Communication Speed
19200/9600/4800/2400/19200 bps User Selectable
Control Procedure
Asynchronous Communication System
Communication System
Half duplex system
Character System
ASCII (8 bit)
Stop Bit Length
1 bit
Error Check (CRC16)
2 byte
Parity check
None
7.4.4
12Bit Binary (DI) Input
Category
Specification
BIT
Digital 12Bit input
Communication
Install on the Control Board of Inverter using option connector (CN2)
Control Board
Powered by Inverter
Power
Supply
24V Power
Powered by Inverter 24V using connector
7.4.5
Installing Option Board
Connect the option board to Control board using Connector CN2.
CN2
Connector
Mounting
poles
Option board
Control board
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]