56
CHAPTER 5 -
PARAMETER LIST
5.1 Drive Group [DRV]
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
DRV-00
11
Command Frequency or
Command Torque
(Output Frequency/
Torque during motor run,
Reference Frequency/
Torque during motor
stop)
Output Current (LCD)
Cmd. freq
or
Cmd. Trq
F or r
(DRV-13)
0 to FU1-20 (Max. freq)
0.01
0.00 [Hz]
Yes
79
DRV-01
Acceleration Time
Acc. time
01
0 to 6000
0.1
20.0 [sec]
Yes
80
DRV-02
Deceleration Time
Dec. time
02
0 to 6000
0.1
30.0 [sec]
Yes
81
Keypad
0
Fx/Rx -1
1
DRV-03
Drive Mode
(Run/Stop Method)
Drive mode
03
Fx/Rx -2
2
-
Fx/Rx -1
No
81
Keypad-1
0
Keypad-2
1
V1
2
I
3
DRV-04
Frequency Mode or
Torque Mode
(Frequency/Torque
setting Method)
Freq mode
or
Torque mode
04
V1+I
4
-
Keypad-1
No
82
DRV-05
Step Frequency 1
Step freq-1
05
10.00 [Hz]
DRV-06
Step Frequency 2
Step freq-2
06
20.00 [Hz]
DRV-07
Step Frequency 3
Step freq-3
07
0 to FU1-20
(0 to Max. freq)
0.01
30.00 [Hz]
Yes
83
DRV-08
Output Current
Current
08
Load Current in RMS
-
[A]
-
84
DRV-09
Motor Speed
Speed
09
Motor Speed in rpm
-
[rpm]
-
84
DRV-10
DC link Voltage
DC link Vtg
10
DC Link Voltage inside inverter
-
[V]
-
84
DRV-11
User Display Selection
User disp
11
Selected in FU2-73 (User Disp)
-
-
-
84
DRV-12
Fault Display
Fault
12
-
-
-
None
nOn
-
84
0 [
F
orward]
DRV-13
Motor Direction Set
Not displayed in
LCD keypad
13
Not available
1 [
r
everse]
-
0
Yes
85
DRV-14
Target/Output Frequency
Display
Tar/Out Freq.
14
-
-
-
0.00 [Hz]
Yes
85
DRV-15
12
Reference/Feedback
Frequency Display
Ref/Fbk Freq.
15
-
-
-
0.00 [Hz]
Yes
85
Hz disp
0
DRV-16
Speed Unit Selection
Hz/Rpm Disp
16
Rpm disp
1
-
-
Yes
85
DRV-20 FU1
Group Selection
20
85
DRV-21 FU2
Group Selection
21
85
DRV-22 I/O
Group Selection
22
85
DRV-23
13
EXT
Group Selection
Not displayed in
LCD keypad
23
Not available
Press
[PROG/ENT]
key
-
1
Yes
85
11
The speed unit is changed to [%] when FU2-39 is set to ‘Sensorless_T’ or ‘Vector_TRQ’.
12
Code DRV-15 appears only when FU2-47 is set to ‘Yes’.
13
Code DRV-23 through DRV-24 appears only when a Sub-Board or an Option Board is installed.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]