Chapter 6 - Parameter Description [FU2]
115
Setting
Range
Description
0
DRV-00 [Command Frequency]
1
DRV-01 [Acceleration Time]
2
DRV-02 [Deceleration Time]
3
DRV-03 [Drive Mode]
4
DRV-04 [Frequency Mode]
5
DRV-05 [Step Frequency 1]
6
DRV-06 [Step Frequency 2]
7
DRV-07 [Step Frequency 3]
8
DRV-08 [Output Current]
9
DRV-09 [Motor Speed]
10
DRV-10 [DC link Voltage
11
DRV-11 [User Display selected in FU2-73]
12
DRV-12 [Fault Display]
FU2-73: User display selection
Related Function
: DRV-11 [User display selection]
Select the display as shown below in FU2-73 [User
display selection].
Setting
FU2-73
Name
Description
0
Voltage
Output
voltage
Display output voltage of
the inverter (Factory
setting)
1
Watt
Output
power
Display output power of the
inverter
☞
Note:
The displayed vlaue of “Watt” is approximate
value.
FU2-74: Gain for Motor Speed Display
This code is used to change the motor speed display to
rotating speed (r/min) or mechanical speed (m/min). The
display is calculated by following equation.
Rotating speed = 120 x F / P, where F=Output frequency,
P= motor pole number
Mechanical speed = Rotating speed x Motor RPM
Display Gain
FU2-75: DB (Dynamic Braking) Resistor Mode
Selection
This code is used to protect the DB resistor from over
heating.
Setting Range
LCD
7-Seg
Description
None
0
This is selected when there is no resistor
connected. At this time, inverter does not
generate DB turn on signal.
Int. DB-R
1
This is selected when using the internal
DB resistor. This must be selected for
1~5 HP inverters because they have
internal DB resistor as a default.
Enable Duty (%): 2 ~ 3 %
Continuous Turn On Time: 5 seconds
Ext. DB-R
2
This is selected when using an external
DB resistor. This must be selected for
1
~
3
0 HP inverters. This must be selected
for 1~5 HP inverters in case of using an
external DB resistor.
Enable Duty (%): 0 ~ 30 %
Continuous Turn On Time: 15 seconds
l
The inverter turns the DB turn on signal OFF when the
Continuous Turn On Time expires during dynamic
braking, and an over voltage fault could occur. When this
happens, increase the deceleration time or install an
external high-duty DB resistor.
l
Install an exterior high-duty DB resistor when the load
accelerates and decelerates frequently. Set the FU2-75
[DB Resistor Mode selection] to ‘Ext. DB-R’, and set the
FU2-76 [Duty of DB Resistor].
Refer to Basic Wiring in
Chapter 1. Installation or Power Terminal Wiring.
l
This does not apply to
40~100
HP inverters. They need
the Optional DB unit to use DB resistor.
FU2-76: Duty of DB (Dynamic Braking) Resistor
FU2? RPM factor
74 100 %
100
74
Factory Default:
100 %
100
FU2? DB mode
75 Int. DB-R
1
75
Factory Default:
Int. DB-R
1
Related Functions:
DRV-00 [Output Frequency]
DRV-09 [Motor Speed]
FU2-31 [Number of Motor Pole]
FU2? DB %ED
76 10 %
10
76
Factory Default:
10 %
10