Chapter 5 - Parameter Description [I/O]
118
6.4 Input/Output Group [I/O]
I/O-00: Jump to Desired Code #
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.
I/O-01 ~ I/O-05: Analog Voltage Input (V1) Signal
Adjustment
This is used to adjust the analog voltage input signal
when the frequency is referenced by the control terminal
‘V1’. This function is applied when DRV-04 is set to ‘V1’
or ‘V1+I’. Reference frequency versus Analog voltage
input curve can be made by four parameters of I/O-02 ~
I/O-04.
This is the filtering time constant for V1 signal input.
Increase this value if the V1 signal is affected by noise
causing unstable operation of the inverter. Increasing
this value makes response time slower.
This is the minimum voltage of the V1 input at which
inverter outputs minimum frequency.
This is the inverter output minimum frequency when
there is the minimum voltage (I/O-02) on the V1 terminal.
In torque mode, the display is changed to [%].
This is the maximum voltage of the V1 input at which
inverter outputs maximum frequency.
This is the inverter output maximum frequency when
there is the maximum voltage (I/O-03) on the V1 terminal.
In torque mode, the display is changed to [%].
Setting FU2-39 [Control mode select] to Vector_Torque
or Sensorless_T, the setting value is changed to Torque
value as below.
Code
Factory Default
Setting Range
I/O-02
0 [V]
0 ~ 10 [V]
I/O-03
0 [%]
0 ~ 150[%]
I/O-04
10 [V]
0 ~ 10 [V]
I/O-05
100 [%]
0 ~ 150[%]
[Reference Frequency vs. Analog Voltage Input, V1 (0 to 10V)]
I/O-06 ~ I/O-10: Analog Current Input (I) Signal
Adjustment
This is used to adjust the analog current input signal
when the terminal ‘I’ references the frequency. This
function is applied when DRV-04 is set to ‘V1’ or V1+I’.
Reference frequency versus Analog current input curve
can be made by four parameters of I/O-07 ~ I/O-10.
I/O? Jump code
00 1
Factory Default:
1
I/O? V1 filter
01 10 ms
10
01
Factory Default:
10 ms
10
I/O? V1 volt x1
02 0.00 V
0.00
02
Factory Default:
0.00 V
0.00
I/O? V1 freq y1
03 0.00 Hz
0.00
03
Factory Default:
0.00 Hz
0.00
I/O? V1 volt x2
04 0.00 V
10.00
04
Factory Default:
10.00 V
10.00
I/O? V1 freq y2
05 60.00 Hz
60.00
05
Factory Default:
60.00 Hz
60.00
Reference Frequency
I/O-05
Analog Voltage
Input (V1)
I/O-03
I/O-02
I/O-04
Related Functions:
DRV-04 [Frequency Mode]
FU1-20 [Maximum Frequency]