Chapter 6 - Parameter Description [I/O]
122
[XCEL-L, XCEL-M, XCEL-H]
By setting P1, P2 and P3 terminals to ‘XCEL-L’, ‘XCEL-
M’ and ‘XCEL-H’ respectively, up to 8 different Accel and
Decel times can be used. The Accel/Decel time is set in
DRV-01 ~ DRV-02 and I/O-25 ~ I/O-38.
The Accel/Decel time is determined by the combination
of P1, P2 and P3 terminals as shown in the following
table.
Accel/Decel
Time
Parameter
Code
XCEL-H
(P3)
XCEL-M
(P2)
XCEL-L
(P1)
Accel Time-0
DRV-01
Decel Time-0
DRV-02
0
0
0
Accel Time-1
I/O-25
Decel Time-1
I/O-26
0
0
1
Accel Time-2
I/O-27
Decel Time-2
I/O-28
0
1
0
Accel Time-3
I/O-29
Decel Time-3
I/O-30
0
1
1
Accel Time-4
I/O-31
Decel Time-4
I/O-32
1
0
0
Accel Time-5
I/O-34
Decel Time-5
I/O-35
1
0
1
Accel Time-6
I/O-36
Decel Time-6
I/O-37
1
1
0
Accel Time-7
I/O-38
Decel Time-7
I/O-39
1
1
1
0: OFF, 1: ON
[Multi-Accel/Decel Time Operation]
[Dc-brake]
DC Injection Braking can be activated during inverter
stopped by configuring one of the multi-function input
terminals (P1, P2, P3) to ‘Dc-bake’. To activate the DC
Injection Braking, close the contact on the assigned
terminal while the inverter is stopped.
[Exchange]
Exchange is used to bypass the motor from the inverter
line to commercial power or the opposite. To bypass the
motor to commercial line, set the ‘Exchange’ function in
multi-function output terminal and ‘INV line’, ‘COMM line’
function in multi-function output terminal. Speed search
function (FU2-22) is activated automatically during
exchanging operation.
M2
U
V
W
G
R
S
T
FX
RX
P1
P3
CM
VR
V1
I
5G
FM
5G
30A
30B
30C
AXA
AXC
P2
MOTOR
Potentiometer
(1 kohm, 1/2W)
Speed signal Input
2
Forward Run/Stop
Reverse Run/Stop
‘Exchange’
Common Terminal
Factory Setting:
‘Speed -L’
‘Speed -M’
‘Speed -H’
Power supply for
speed signal:
+ 11V, 10mA
Speed signal input:
0 ~ 10V
Speed signal input:
4 ~20mA (250ohm)
Common for
VR, V1, I
Shield
MCCB
M1
M2
AC220V Line
M1
M1
[Wiring to By-Pass Motor to Commercial line]
P1-CM
ON
Output Frequency
Time
Time
P2-CM
ON
Time
P3-CM
ON
Time
FX-CM
ON
Time
ON
ON
ON
ON
Ref.
Freq.
Time 0 Time 1 Time 2 Time 3 Time 4 Time 5 Time 6 Time 7
Related Functions:
I/O-25 ~ I/O-38 [1
st
~7
th
Accel/Decel Time]