Chapter 6 - Parameter Description [APP]
152
Draw & Override
Gain/Bias
I/O-2~5
DRV-5
DRV-6
I/O-1
DRV-0
DRV-4
Frequency Mode
Reference Frequency
Miti-Step
Frequency
I/O-12 ~ 14
LPF
Step2
V1
Control
Terminal
EXT-2 ~ 4
DRV-7
I/O-21
I/O-22
I/O-23
I/O-24
keypad-1
keypad-2
Gain/Bias
I/O-7~10
I/O-6
LPF
I
Control
Termianl
V1
SUB-A
or SUB-C
Gain/Bias
EXT-7~10
EXT-6
LPF
V2
None
I
V1+I
FU1-20
Max.
Frequency
Limit
wTarFreq
None
APP-33
DrawPerc (%)
Override_Freq
Draw_Freq
EXT-5 V2 Mode
Override
Step1
Step3
Step4
Step5
Step6
Step7
APP-33
Draw Mode
Code
LCD Display
Description
Factory Default
Setting Range
APP-33
Draw Mode
Draw Mode Select
0(None)
0(None)
1(V1_Draw)
2(I_Draw)
3(V2_Draw)*
APP-34
DrawPerc
Draw Size Setting
100.0%
0.0 – 150.0%
☞
Note:
1. APP-33 Setting Guide: Ref. Frequency setting mode should not be duplicated:
Ref. Freq Setting: DRV-04 [V1] APP-33 [Draw Mode]: 1(V1_Draw) (X)
Ref. Freq Setting: DRV-04 [V1] APP-33 [Draw Mode]: 2(I_Draw) (O)
2. APP-34 sets the freq limit scale during Draw Mode.
Ex) If Ref freq (Keypad -1)=30Hz, APP-33=1(V1_Draw), APP-34=10%, the ref freq for Draw mode will be
issued from 27Hz to 33Hz.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]