Chapter 2 - Operation
34
Operation
Example (1)
Freq Setting via Run/Stop via Terminal (FX/RX)
[Operation condition]
-. Control mode: V/F control
-. Ref. Frequency: 50[Hz] setting via keypad
-. Accel/Decel time: Accel – 10 [Sec], Decel – 20 [Sec]
-. Drive mode: Run/Stop via FX/RX terminal
[Wiring]
R
S
T
G
U
V
W
B1
B2
FX
RX
BX
RST
JOG
P1
P2
P3
CM
VR
V1
5G
FM
5G
30A
30C
30B
AXA
AXC
IM
3P
AC
input
Potentiometer
1[kohm],1/2W
S/W
Step
Parameter setting
Code
Description
1
Control Mode Selection
FU2-39
Set it to 0 {V/F}.
2
Drive Mode
DRV-3
Set it to 1 Fx/Rx-1.
3
Frequency Mode
DRV-4
Set it to 0 Keypad-1.
4
50[Hz] freq command
setting
DRV-0
Set freq command 50[Hz] via Keypad.
5
Accel/Decel time
DRV-2
DRV-3
Set Accel time to 10 [Sec] in DRV-2.
Set Decel time to 20 [Sec] in DRV-3.
6
Terminal FX
Motor starts to rotate in Forward direction at 50Hz with Accel time
10 [sec] when FX terminal is turned ON.
Motor decelerates to stop with Decel time 25[sec] when FX
terminal is turned OFF.
7
Terminal RX
When RX terminal is turned ON motor starts to rotate in Reverse
direction at 50[Hz] with Accel time 10 [Hz]. When it is OFF, motor
decelerates to stop with Decel time 20 [Sec].