Chapter 6 - Parameter Description [I/O]
125
[Hold step]
This is used to hold the last step frequency in Auto-A
operation.
[‘Go step’ in Auto-B Operation]
[‘Hold step’ in Auto-A Operation]
[Trv Off.Lo]
This function is used to make negative offset during
traverse operation.
[Trv Off.Hi]
This function is used to make positive offset during
traverse operation.
[Interlock1, 2, 3, 4]
This function is used for MMC operation. Refer to MMC
operation.
[Reset]
This function is set to use it as fault reset terminal when
ON.
[BX]
This function is set to use it as Emergency Stop terminal
when ON.
[JOG]
This function is set to use Jog operation terminal when
ON.
[FX]
This function is set to issue Forward Run.
[RX]
This function is set to issue Reverse Run.
[Ana Change]
Inverter changes its frequency reference source from V1
to I when ON.
[Pre excite]
This setting switches the inverter in pre-exciting state
when assignning Pre excite to the desired terminal. This
function applies only the exciting current to a motor in
Sensorless_S control. In Vector_SPD control, the
inverter conducts pre-exciting to start a motor after the
magnetic -flux is established and holding torque, even
200% of motor nominal torque is guaranteed. When the
operation command is set to ON, the state changes from
pre-exciting to normal.
Related Functions:
I/O-51 ~ I/O-84 [Sequence Operation]
Time
P1-CM
‘SEQ-L’
ON
Output Frequency
Time
ON
Time
ON
Time
P2-CM
‘SEQ-M’
P3-CM
‘Go step’
ON
ON
ON
ON
Minimum 100msec
SEQ1 / 2F
SEQ2 / 2F
SEQ1 / 1F
SEQ3 / 2F
SEQ3 / 1F
Sequence 1
Sequence 3
Sequence 2
P1-CM
‘SEQ-L’
Output Frequency
Time
Time
Time
P2-CM
‘SEQ-M’
P3-CM
‘Hold step’
ON
SEQ2 / 2F
SEQ1 / 2F
SEQ2 / 1F
SEQ1 / 1F
Sequence 1
Sequence 2
ON
ON
Time
Related Functions:
APP-06 ~ APP-07 [Traverse Offset]
Related Functions:
APP-06 ~ APP-07 [Traverse Offset]
Related Functions:
APP-29 [Inter-Lock Selection]