Chapter 2 - Operation
32
2.4 Operation Method
The iS5 has several operation methods as shown below.
Operation Method
Function
Function Setting
Operation using
Keypad
Run/Stop command and frequency are set only through the
keypad.
DRV 03: Keypad
DRV 04: Keypad-1 or -2
Operation using
Control Terminals
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through V1 or I or V1+I terminal.
DRV 03: Fx/Rx-1 or -2
DRV 04: V1 or I or V1+I
Run/Stop is performed by the keypad.
Frequency reference is set through the V1 or I or V1+I
terminal.
DRV 03: Keypad-1 or -2
DRV 04: V1 or I or V1+I
Operation using both
Keypad and Control
Terminals
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through the keypad.
DRV 03: Fx/Rx-1 or -2
DRV 04: Keypad-1 or -2
Operation using
Option Board
Operation using option board.
The iS5 has five option boards and three sub-boards.
Option Boards:
RS485, Device-Net, F-Net, ProfiBus and
ModBus
Sub-Boards:
Sub-A Board, Sub-B Board, Sub-C Board
(Please refer to ‘Chapter 7 - Options’ for more information.)
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]