Chapter 5 - Parameter List
61
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
1.5kW
1
2.2kW
2
3.7kW
3
5.5kW
4
7.5kW
5
11.0kW
6
15.0kW
7
18.5kW
8
22.0kW
9
30.0 kW
10
37.0 kW
11
45.0 kW
12
55.0 kW
13
75.0 kW
14
FU2-31
Number of Motor Poles
Pole number
31
2 to 12
1
4
No
104
FU2-32
Rated Motor Slip
Rated-Slip
32
0 t o10 [Hz]
0.01
No
104
FU2-33
Rated Motor Current
(RMS)
Rated-Curr
33
1 to 200 [A]
1
No
104
FU2-34
No Load Motor Current
(RMS)
Noload-Curr
34
0.5 to 200 [A]
1
No
104
FU2-35
Motor Rated Voltage
Motor Volt
35
180..460 [V]
No
104
FU2-36
Motor Efficiency
Efficiency
36
70 to 100 [%]
1
20
No
104
FU2-37
Load Inertia
Inertia rate
37
0 to 1
1
0
No
104
FU2-38
Carrier Frequency
Carrier freq
38
1 to 15 [kHz]
1
5 [kHz]
Yes
106
V/F
0
Slip comp
1
Sensorless_S
2
Sensorless_T
3
Vector_SPD
4
FU2-39
Control Mode Selection
Control mode
40
Vector_TRQ
5
-
V/F
No
106
No
0
All
1
Rs + Lsigma
2
Enc Test
3
FU2-40
Auto Tuning
Auto tuning
41
Tr
4
-
No
No
FU2-41
21
Stator Resistance of
Motor
Rs
42
0 to (depend on FU2-30) [ohm]
0.001
No
FU2-42
Leakage Inductance of
Motor
Lsigma
44
0 to (depend on FU2-30) [mH]
0.001
No
FU2-43
Stator Inductance of
Motor
Ls
43
0 to (depend on FU2-30) [mH]
22
No
108
19
The rated motor is automatically set according to the inverter model name. If different, set the motor capacity connected.
20
This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.
21
Code FU2-41 through FU2-46 appears only when FU2-39 is set to ‘Sensorless_X’ or ‘Vector_XXX’.
22
This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.