Chapter 5 - Parameter List
76
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
APP-09
Starting Aux. Motor
Selection
Starting Aux
09
1 to 4
1
1
Yes
147
APP-10
Operation Time Display
on Auto Change
Auto Op Time
10
-
-
-
-
147
APP-11
Start Frequency of Aux.
Motor 1
Start freq 1
11
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-12
Start Frequency of Aux.
Motor 2
Start freq 2
12
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-13
Start Frequency of Aux.
Motor 3
Start freq 3
13
0 to FU1-20
0.01 49.99 [Hz] Yes
APP-14
Start Frequency of Aux.
Motor 4
Start freq 4
14
0 to FU1-20
0.01 49.99 [Hz] Yes
147
APP-15
Stop Frequency of Aux.
Motor 1
Stop freq 1
15
0 to FU1-20
0.01 15.00 [Hz] Yes
APP-16
Stop Frequency of Aux.
Motor 2
Stop freq 2
16
0 to FU1-20
0.01 15.00 [Hz] Yes
APP-17
Stop Frequency of Aux.
Motor 3
Stop freq 3
17
0 to FU1-20
0.01 15.00 [Hz]] Yes
APP-18
Stop Frequency of Aux.
Motor 4
Stop freq 4
18
0 to FU1-20
0.01 15.00 [Hz] Yes
148
APP-19
Delay Time before
Operating Aux Motor
Aux start DT
19
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
APP-20
Delay Time before
Stopping Aux Motor
Aux stop DT
20
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
148
APP-21
The Number of Aux Motor
Nbr Aux’s
21
0 to 4
1
4
Yes
148
No
0
APP-22
PID Bypass Selection
Regul Bypass
22
Yes
1
-
No
Yes
148
APP-23
Sleep Delay Time
Sleep Delay
23
0 to 9999 [sec]
0.1
60.0 [sec]
Yes
149
APP-24
Sleep Frequency
Sleep Freq
24
0 to FU1-20
0.01
0.19 [Hz]
Yes
149
APP-25
Wake-Up Level
WakeUp Level
25
0 to 100 [%]
1
35.0 [%]
Yes
149
APP-26
Auto Change Mode
Selection
AutoCh-Mode
26
0 to 2
1
1
Yes
149
APP-27
Auto Change Time
AutoEx-intv
27
00:00 to 99:00
00:01
72:00
Yes
APP-28
Auto Change Level
AutoEx-level
28
0 to 100 [%]
0.1
20 [%]
Yes
150
No
0
APP-29
Inter-Lock Selection
Inter-lock
29
Yes
1
-
No
Yes
150
APP-30
Feedback Freq/
Percentage Display
Fbk/PER
30
[Hz] / [%]
-
150
APP-31
Actual Value Display
Prs
31
[Bar]/[Pa]
-
-
-
-
151
APP-32
Pressure Display Scale
Scale Disp
32
0 to 50000
-
1000
Yes
151
None
0
V1_Draw
1
I_Draw
2
APP-33
30
Draw Mode Selection
Draw Mode
33
V2_Draw
3
-
None
Yes
151
APP-34
Draw Size Setting
DrawPerc
34
0 to 150 [%]
0.1
100 [%]
Yes
151
30
Code APP-32 through APP-33 appears only when APP-01 is set to ‘Draw’.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]